Hot New Products BS31 Conduit Pipe - Electrical Conduit Pipe EMT – Rainbow
Hot New Products BS31 Conduit Pipe - Electrical Conduit Pipe EMT – Rainbow Detail:
Electrical Metallic Tubing
Electrical metallic tubing (EMT), also commonly called thin-wall, is a listed steel raceway of circular cross section, which is unthreaded, and nominally 10′ long. 20′ lengths are also available. EMT is available in trade sizes 1/2 through 4. The outside is galvanized for corrosion protection and the inside has an approved corrosion-resistant organic coating. EMT is installed by use of set-screw or compression-type couplings and connectors. It is permitted to have an integral coupling comprised of an expanded, “belled” shape tube on one end with set screws. EMT with integral couplings is available in trade sizes 1-1/4 through 4.
Applicable Tolerance:
Outside Diameter : ±0.005in(0.13 mm)
Wall Thickness: +10%~ -5%
The wall thickness shall not vary more than 0.003in(0.08mm) throughout a 10 foot length
Length:±0.25 in (6.4 mm)
Standard: UL797-2000
Finishes: Zinc Plated, Pre-galvanized
Zinc coated: class 3, 80-120 g/m2; class 4, 275-500 g/m2
Package: 1.Big OD: in bulk;
2.Small OD: in bundles, packed by steel strips;
3.Waterproof package with plastic cloth;
4.Standard export package;
5.According to customers’ requirements.
Size |
Outside Diameter |
Inside Diameter |
|
|
||||
inch |
inch |
mm |
inch |
mm |
(1)mm |
(2)mm |
feet |
mm |
1/2” |
0.706 |
17.93 |
0.622 |
15.80 |
1.07 |
0.85 |
10 |
3050 |
3/4” |
0.922 |
23.42 |
0.824 |
20.93 |
1.25 |
1.00 |
10 |
3050 |
1” |
1.163 |
29.54 |
1.049 |
26.64 |
1.45 |
1.10 |
10 |
3050 |
1-1/4” |
1.510 |
38.35 |
1.380 |
35.05 |
1.65 |
1.30 |
10 |
3050 |
1-1/2” |
1.740 |
44.20 |
1.610 |
40.89 |
1.65 |
1.30 |
10 |
3050 |
2” |
2.197 |
55.80 |
2.067 |
52.50 |
1.65 |
1.40 |
10 |
3050 |
2-1/2” |
2.875 |
73.00 |
2.731 |
69.37 |
1.83 |
- |
10 |
3050 |
3” |
3.500 |
88.90 |
3.356 |
85.24 |
1.83 |
- |
10 |
3050 |
3-1/2” |
4.000 |
101.60 |
3.834 |
97.38 |
2.11 |
- |
10 |
3050 |
4” |
4.500 |
114.30 |
4.334 |
110.08 |
2.11 |
- |
10 |
3050 |
Applications:
Conduit pipe is generally installed by electricians at the site of installation of electrical equipment. It is used to protect and route electrical wiring in a building or nonbuilding structure.
Product detail pictures:
Related Product Guide:
Fire protection measures for steel structures
Technical Specification for safety of steel pipe scaffold for construction
Our advancement depends over the highly developed devices, excellent talents and continually strengthened technology forces for Hot New Products BS31 Conduit Pipe - Electrical Conduit Pipe EMT – Rainbow , The product will supply to all over the world, such as: Malta, Munich, Denmark, Selling our products causes no risks and brings high returns to your company instead. It is our consistent pursuit to create value for clients. Our company is looking for agents sincerely. What are you waiting for? Come and join us. Now or never.